Transforming a heritage building into a high-performance public establishment, while preserving its large glass facades and foregoing conventional air conditioning: this is the technical challenge undertaken at the Chalet du parc de la Tête d'Or, in Lyon.
The project, led by developer Youse in collaboration with the firm Looking For Architecture, aims to transform this building, closed for thirteen years, into a space dedicated to ecological transition. Oteis was involved from the competition phase onward, handling the electrical, heating, ventilation, air conditioning (HVAC), and plumbing work.
The reopening is scheduled for September 18, 2026, with a target of 300.000 visitors per year. The project aims for EnerPHit Plus certification, a standard developed by the Passive House Institute for high-performance energy renovation of existing buildings.
The performance figures announced by Oteis17,7 kWh/(m².year) heating requirement, compared to an EnerPHit threshold of 20 kWh/(m².year) An apparent COP of around 25 for geocooling using groundwater 25 air changes per hour targeted by natural nighttime ventilation 3.350 m³ of greywater that could be reused each year |
A design guided by the EnerPHit Plus objective
The pursuit of energy efficiency encompassed all aspects of the building's use, including the restaurant kitchen's energy consumption. The design of the technical installations was based on two main principles: significantly reducing heating needs and avoiding the use of conventional air conditioning.
According to Oteis, the calculated heating requirement is 17,7 kWh/(m².year), below the 20 kWh/(m².year) threshold specified for the project. Specific work was done to ensure the airtightness of the building envelope in order to minimize heat loss and the risk of overheating, despite the preservation of the historic glazed facades.
The strategy must also enable the Chalet to achieve a positive energy balance, a condition associated with the EnerPHit Plus label. However, this performance remains contingent upon actually obtaining certification and the results observed after the building is commissioned.
The Rhône aquifer is used for heating and cooling.
The proximity of the Rhône aquifer, located according to the engineer at a depth of only two to three meters, constitutes the project's main energy resource. The system relies on a water-to-water heat pump supplied by a well and supplemented by a discharge well.
In winter, the heat pump must provide heating and hot water production with an announced coefficient of performance (COP) of around 5. Radiators placed along the glazed facades complement the hot air diffused by the air handling units, whose power was not sufficient to compensate alone for the losses of these historic surfaces.
In summer, the system directly uses the groundwater temperature via a heat exchanger. This geocooling avoids putting stress on the heat pump's compressor and, according to Oteis, achieves an apparent COP of over 25.
The hydraulic distribution system operates using a variable flow loop. Water circulation is thus adjusted to instantaneous needs in order to reduce the electrical consumption of the pumps.
Three levels of response to extreme heat
To address the increasing frequency of heatwaves in Lyon, the summer comfort strategy combines passive and semi-active solutions. Its operation adapts to indoor conditions.
Sun protection and automated night ventilation
Automated sunshades limit heat gain during the day. At night, openings provide natural cross-ventilation, taking advantage of the cooler temperatures in the park.
These openings are connected to the building management system (BMS), which controls their opening and closing, particularly when the premises are unoccupied. The system aims for an air exchange rate of 25 volumes per hour, compared to 2,5 volumes per hour for conventional free cooling cited by Oteis.
When conditions require it, the air handling units can also be supplied with water tempered by the geocooling system.
Ventilation adapted to different uses
The building will house a restaurant, a kitchen, exhibition spaces, awareness areas, and conference rooms. Several dual-flow air handling units have therefore been divided into sectors according to their uses:
- a central kitchen unit, sized for a production of more than 150 meals per day, with extraction hoods and diffusion via micro-perforated duct;
- power plants dedicated to exhibition, awareness and conference spaces, whose flow rate will be regulated by carbon dioxide probes according to occupancy;
- an M6/F9 filtration system adapted to the urban context, combined with heat recovery from the extracted air whose advertised efficiency exceeds 80%.
Oteis indicates that this filtration should retain approximately 95% of PM10 particles.
Air circulators before the geocooling is activated
From 26°C, air circulators must lower the perceived temperature by 2 to 4°C with limited electricity consumption. When the temperature reaches 28°C, geocooling is activated via chilled floors and air handling units.
The system has also been designed to adapt. If heat waves become more intense, the heat pump can be switched to active operation to increase cooling capacity.
Reuse extended to technical batches
The reuse approach also applies to fluid and electrical components. Cable trays come from reuse channels in the Lyon metropolitan area, while some existing sanitary fixtures have been retained and put back into service after assessment.
Oteis also oversaw the restoration of the Chalet's monumental chandelier. This fixture, over two meters in diameter, was removed, cleaned, and then reinstalled before the building reopened.
A greywater reuse system
The project aims to treat greywater from kitchens for reuse in applications that do not require drinking water. The system combines biological filtration, an ultrafiltration membrane, activated carbon, and ultraviolet treatment.
After treatment, this water is intended to supply toilets, water green spaces, maintain surfaces, and cool beer taps. Oteis estimates that 3.350 m³ of this water can be reused annually.
A construction site constrained in the heart of a busy park
The work began with asbestos removal and interior demolition. It was carried out within a limited area in a park that remained accessible to the public from 6 a.m. to 21 p.m., requiring precise organization of traffic flow and deliveries.
The lack of up-to-date plans and discoveries made during construction necessitated several adjustments. In particular, the change in the kitchen design during the project led to a revision of some of the studies concerning what was presented as the building's largest energy consumer.
“On a building that had remained closed for thirteen years, without updated plans, we had to deal with constant discoveries as the work progressed. Added to this was a change in the kitchen concept decided mid-construction by the restaurateur, which called into question some of our studies already underway on the building's biggest energy consumer. Meeting an energy objective as demanding as the EnerPHit label for a public establishment, with tight deadlines and budgets, required constant adjustments with all the project teams,” explains Nicolas Schiavolini, head of the building services team at Oteis on this project.
In this heritage project, any modification to the uses or equipment is likely to affect the overall energy balance. The stated performance levels will therefore need to be confirmed after the completion of the construction work, the commissioning of the installations, and the potential attainment of EnerPHit Plus certification.